Extensions - IP Powermeter

Measure power consumption, reduce costs sustainably

ALLNET Powermeters help you to identify load peaks and power consumers and to reduce power consumption sustainably on the basis of the measured values. The ALLNET Powermeters can directly access the three phases of the power line and thus provide exact consumption data. The consumption data is tapped via induction terminals without the need to intervene in the house wiring. This increases safety and convenience in equal measure and allows uncomplicated use in any application scenario. Numerous network functions allow individual further processing with the ALLNET sensor meters, as well as targeted evaluation and archiving of the data.

Inductive power clamps 50A, 200A & 800A

"The compact divisible cable conversion current transformers (50A & 200A) are especially suitable for retrofitting in existing installations. Cable conversion current transformers are particularly used in cases where the current path must not be interrupted.
For the 800A transformers, the current path must be interrupted and the power cable must be passed through the transformer. "

S0 - Pulse generator

"The S0 interface is used by gas meters, water meters, electricity meters, heat meters and for general consumption measurement in building automation.
The meter readings are transmitted by pulses. The signal is generated by the meter as a current pulse. A current flow of less than 3 mA corresponds to a LOW value. If the current flow is greater, this is interpreted as a HIGH value."

D0, SML, OBIS Key figures

"Modern electronic household meters (digital meters) have an optical front interface (infrared), which is designed according to the requirements of the

-DIN EN 62056-21: Meter reading transmission, tariff and load control Part 21: Data transmission for fixed and mobile connection
-SML: Smart metering language, a communication protocol for electricity meters.

is structured.

For example, bidirectional meters for photovoltaic systems are prescribed by the network operator as digital electricity meters; these usually have this so-called D0 infrared interface. The reading is done with a D0 reading head and the corresponding power meter. The recognition of the interface protocol and the identification by means of OBIS codes, reference and feed-in data can then be recorded and displayed in separate channels. Although there is a D0 standard, unfortunately the manufacturers of the power meters do not adhere to it. This means that the last bits and bytes of these OBIS key figures are unfortunately not identical for all of them. This has led to the fact that we keep a compatibility list and only the electricity meters which are included in the list can be used.

Recommendation: Buy a compatible D0 electricity meter (see compatibility list) and install it behind your current electricity meter from your energy supplier. Why? Even if the current electricity meter installed by your utility is compatible with our system, it is possible that it will be replaced at any time. This would, of course, cause your installation to stop working from that point on.

Differences between the power meters

Powermeters


 
pdf-download 109096-1  Art. nr. 109096

> Zum Online Shop

Know what's going on!

Find power guzzlers!

Analyzing power consumption!

Save electricity!

 

Highlight:

  • Meter to measure and control your current power consumption
  • Direct connection of the current phases up to 32A per phase.
  • Current measurement via integrated shunts
  • Can be accessed anywhere via the Internet (Internet connection at the ALL3967 location is required)
  • Simple operation and installation through web interface
  • Integrated web server
  • Alerting by email when a preset value is exceeded
  • 1x I2C port for additional sensors/actuators of the ALLNET MSR measurement control rules series
  • Comprehensive consumption display with live diagram, chart function, table display, etc.
  • Possibility to download the measured values in database format, e. g. as CSV file
  • Interfaces: 1x network, 1x USB, 1x I2C,
  • Connection of the 3 phases L1/L2/L3/N

 

 Features and WebGUI:

 

 


 

The power meter offers you the possibility to graphically display your consumption. You can display a daily, weekly, monthly or annual graph and show or hide individual phases.

 

The configuration page of the power meter allows you to set individual values within the device. Example: Labels and graph colours.

 




If you want to continue using the determined values of the power meter or if you want to export them for archiving, you can easily download them as a CSV file via the web menu. Of course, there is also the chance to call up the values live via JSON.

Technische Daten:

 


 

Interfaces:

 

1x Direct Phase Contacts (L1/L2/L3/N) max. 32A

1x I2C Port for additional sensors & actors of ALLNET Building Automation products www.allnet.de/en/allnet-brand/produkte/building-automation/automation-steuer-computer/building-automation-sensors/

1x USB 2.0

4x TTL Outputs

4x Open Collector Output

1x Console RS232

1x OLED-Display

1x LAN 10/100Mbps

1x WIFI 1T1R 150Mpbs

 

Network Connector:

1x RJ45 10/100Mbps

Power supply:

100~240 VAC, 50/60 Hz, internes PSU

Consumption:

<5 Watt maximal

Housing:

DIN-Rail housing 12TE subunits

Environment:

Temperature operation: 0 ~ 40 °C

Operating Humidity: 10% ~ 85% (non-condensing)

Temperature Storage: -20 ~ 60 °C

Humidity Storage: 5% ~ 90% (non-condensing)

Dimensions:

160 x 91 x 63 mm (length x width x height)

Weight:

370 grams (without packaging and accessories)

Marks:

CE, RoHS

Package contents:

 

 

  • 1 piece ALLNET ALL3697
  • QIG Manual
  • 1 Patchcable 1m